TB 1-1730-229-30-3
4.5.7
Operation at Rated Loads.
_____ a. Adjust the load banks as necessary to obtain the following loads and operate for 5 minutes:
Condition:
AC power at 30 KW for the A-Model and 38.4 KW for the D-Model
Hydraulic power at 6.5 GPM 3000 psig
Pneumatic flow between 20-40 psig
Test Start time: _______
Hyd. Flow: _______ GPM
Hydraulic pressure _______ psig
EGT: _______F
Test Stop time: _______
_____ b. De-energize AC load bank and turn pneumatic power to off.
_____ c.
Set hydraulic OUTPUT switch to OFF and set PUMP PRESS switch to DEC (decrease) until
hydraulic output pressure gauge reads approximately 500 psig, or will go no lower.
NOTE
When Hydraulic System power switch is turned to the off position,
pressure should start to drop.
_____ d. Set hydraulic control panel MAIN POWER switch to OFF, and close switch guard.
NOTE
Pressure will still indicate approximately 500 psig.
4.5.8
Operation at Rated Loads.
_____ a. Adjust the load banks as necessary to obtain the following loads and operate for 30 minutes:
Condition:
AC power at 30 KW for the A Model and 38.4 KW for the D Model
DC power at 350 Amps
Test Start time: _______
AC Amps: _______amps
DC Amps: _______amps
EGT: _______F
Test Stop time: _______
_____ b. De-energize load banks.
4.5.9
AC Outlet Tests.
NOTE
Performed with engine running.
_____ a. Assure that all service receptacle circuit breakers are closed.
33