TB 1-1730-229-30-3
Table 2. Functional Inspection Checklist (Continued)
Functional Inspection
Condition
11
If LOW FUEL indicator illuminates, shutdown
and refuel unless operations can be
completed in 30 minutes.
12
If INLET FILTER BLOCKED indicator
illuminates, shutdown and determine cause
of problem; check air intake louvered panel
for obstructions.
13
If COMPT/GEN HI TEMP lamp illuminates,
shut down the AGPU and troubleshoot IAW
TM 55-1730-229-12 and TM 55-1730-229-
34. Record lamp indications prior to setting
MASTER SWITCH to OFF.
14
FAULT INDICATOR illuminates. If automatic
shutdown occurs, record lamp indications
prior to setting MASTER SWITCH to OFF.
15
If Hydraulic control panel red HI TEMP
indicator illuminates, shut down the AGPU
and troubleshoot IAW TM 55-1730-229-12
and TM 55-1730-229-34.
16
Verify operation of DC Power by applying
100 amp load.
Selector Position Specification Voltage Actual
17
Verify operation of battery charger by
Voltage
measuring DC voltage output.
28.5 VDC
26 to 31 VDC
_________
30.5 VDC
28 to 33 VDC
_________
32.5 VDC
29.5 to 34.5 VDC
_________
18
Test operation of both the 400 Hz and 60 Hz,
the operation of the GFCI if so equipped.
19
Test operation of the hydraulic system IAW
20
Test operation of the pneumatic system IAW
21
Verify operation of the Propulsion System
IAW TM 55-1730-229-12 and TM 55-1730-
229-34.
17